Zennio Thermostat: Annex I: Pre-set Values for the PI Control
The tables below show the different profiles for the PI Control that have been pre-set in the Zennio thermostat, together with the corresponding values of K and T.
| Profile | K | T (minutes) |
|---|---|---|
| Warm Water | 5 | 150 |
| Floor Heating | 5 | 240 |
| Electric Heating | 4 | 100 |
| Blow Convector | 4 | 90 |
| A/C Split | 4 | 90 |
Table 3. PI Control Profiles for the Heating Mode
| Profile | K | T (minutes) |
|---|---|---|
| Cooling Ceiling | 5 | 240 |
| Blow Convector | 4 | 90 |
| A/C Split | 4 | 90 |
Table 4. PI Control Profiles for the Cooling Mode
These values have been obtained empirically, and are therefore optimised for the most common climate control contexts. Making use of them is highly encouraged, leaving the manual configuration of these values for very specific situations and for specialists with experience in advanced climate control.